INQUIRY

HOTLINE: +86 20 8489 8493

ONLINE QYY

E-MAIL: info@hncelectric.com

Product > PLC Modules > TX2N-4AD-PT
TX2N-4AD-PT
TX2N-4AD-PT is used for input of platinum Temperature resistance(Pt100 3 lines) temperature sensor.
TX2N-4AD-PT is used for input of platinum Temperature resistance(Pt100 3 lines) temperature sensor.

1) Platinum Temperature resistance(Pt100 3 lines) temperature sensor

2) 4 channels input

3) °C or °F can be used as measured units

4) Accurate Resolution Ratio: 0.2~0.3℃ or 0.36~0.54 °F  Items °C °F

ITEM Centigrade (°C) Fahrenheit (°F)
Input signal 3-wire platinum resistance thermometer sensor Pt100
3850PPM/℃(DIN43760 JIS C1604-1989) or JPt100 3916PPM℃(JIS C1604-1981)
Sensor current 1mA
Rated temperature range -100°C to 600°C -148°F to 1112°F
Digital output -1000 to 6000 -1480 to 11120
Resolution 0.2~0.3°C 0.36 ~0.54°F
Total accuracy ±1.0%
A/D conversion time 15ms*4 channels
Insulation method Photo-coupler isolation between analog and digital circuits.
No isolation between analog channels
Power supply DC5V 30mA(Internal power supplied from the main unit)
DC24V± 10% 50mA(External power supplied)
Occupied points The blocks occupies either 8 input or output points(can be either inputs or outputs)
Applicable PLC LX1N,TX1N,TX2N,TX3U
Weight 0.3kg
Series Model Download
PLC Modules TX2N-4AD-PT User's manual
About HNC
Company Overview Vision and Mission HNC Growth History
Product
PLC HMI PLC Modules CNC Controller Servo Drive Frequency Inverter Spindle Motor AC Servo Motor Accessories
Solution
Packaging & Printing CNC Machine Tool Textile Fan & Pump Converting Elevator Crane Plastic Industry
Service
DownLoad FAQ Warranty
News Centre
HNC news